EasyManua.ls Logo

Toshiba H9 ASD - Page 26

Toshiba H9 ASD
286 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H9 ASD Installation and Operation Manual 19
Figure 4. The Grounding Capacitor
Switch is used on typeforms 230-
volt 0.75 HP to 10 HP and the 25
and 30 HP/460-volt 1.0 HP to 25 HP.
The value may be set to Maximum
(default setting) or to Zero by
pushing or pulling the switch
actuator, respectively.
Figure 5. The Grounding Capacitor
Switch is used on typeforms 230-
volt 15 HP to 20 HP and the 40 HP to
60 HP/460-volt 30 HP to 100 HP.
The value may be set to Large
(default setting) or Small by pushing
or pulling the switch actuator,
respectively.
Figure 6. The Grounding Capacitor
Bar is used on typeforms 230-volt
75 HP and the 100 HP/460-volt 125
HP and the 150 HP.
The value may be set to Large or
Small (default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. The Grounding Capacitor
Screw is used on typeforms 460-volt
200 HP and above.
The value may be set to Large or
Small (default setting) by placing the
screw in the A position or by placing
the screw in the B position,
respectively.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Table of Contents

Other manuals for Toshiba H9 ASD

Related product manuals