Toshiba HFCR407C - [Ab] Pressure Sensor (Pd;Ps) Miswiring

Toshiba HFCR407C
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100
14
Troubleshooting
Diagnostic procedure for check code
Check code Operation cause
[Ab] 1. Connector misconnection of Pd/Ps sensors
Pressure sensor (Pd/Ps) miswiring 2. Pd/Ps sensor error
3. Compressor inverse operation, compressor error
Are the output voltage
characteristics of Pd sensor/Ps
sensor normal ?
Modify wiring.
Check the interface board.
No
No
Is the pipe connection position of
Pd sensor/Ps sensor correct ?
Check connection.
Pd sensor: CN501
Ps sensor: CN500
No
Yes
Yes
Is the wiring of compressor
normal ?
Yes
Are the pressure
characteristics normal when
compressor is operating ?
Check compressor.
No
Yes
Sensor error
[
]