EasyManua.ls Logo

Toshiba HFCR407C - Compressor replacement procedure

Toshiba HFCR407C
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
149
Replacing the compressor
Compressor replacement procedure
After recovery of refrigerant is complete, turn off the power source, and replace the compressor
according to the following method.
[In case of removal of the compressor from the front side]
1. Outdoor units (Inverter and fixed-speed units)
MM-A0280HT, MM-A0224HT, MM-A0280HX, MM-A0224HX
MM-A0280CT, MM-A0224CT, MM-A0280CX, MM-A0224CX
Removing of parts
Remove the front painted panel.
Remove electrical parts cover.
Disconnect all wires connected to the electric parts box.
Temp. sensor, pressure sensor, complete, 2-way valve, PMV, etc.
Remove the electric parts box.
Remove the isolator fixing plate. (Do not remove the pressure sensor.)
Remove the cooling duct for the electric parts.
Remove the crank case heater.
(Only for fixed-speed unit)
Remove the sound-proof blanket.
Remove the terminal cover of the compressor, and remove all wires.
Close the valve located under the compressor fully using a
hexagonal wrench.
Extraction of oil from compressor
Cut the case bypass located at the bottom of the compressor by
the same height as that of the suction pipe.
Connect hose to the cut case bypass, and insert the opposite
side of the hose in the container in which oil is discharged. 7.5 l or
more oil may flow through the hose, so use a container with
capacity of 8 l or more.
Apply nitrogen gas with approx. 0.02MPa from service valve at gas
side to extract oil.
(Extract oil completely.)
Removing of compressor
Remove two discharge pipes, suction pipe, upper oil return piping, oil tank piping, and case bypass piping.
NOTE:
Take great care when removing the pipes with a brazing torch – if oil is remaining in the pipe, a flame may be emitted at the
moment when the flux melts.
Loosen the flare nut at the bottom side of the compressor to remove the pipe.
Remove the screws fixing the bottom plate for the compressor.
Pull out the compressor with the bottom plate for the compressor.
NOTE:
Weight of the compressor is approx. 100kg.
Remove the nuts fixing the compressor.
Remove the compressor.
Bottom plate for
compressor
Brazed positions
to be removed
Case
bypass
pipe
Valve at bottom
side of the
compressor
19

Table of Contents