28
Construction views
Indoor units
2-way cassette
MM-TU028, MM-TU042, MM-TU056
Hanger bolt
(4 x M10)
Drain pipe joint
(outer 25.5)
Refrigerant piping joint
(Liquid 6.4)
Refrigerant piping joint
(Gas 12.7)
Channel for routing TC sensors and
pressure sensor leads
Panel outer dimension 1050
Ceiling opening 1010
Hanging bolt pitch 930
Panel outer dimension 550
Ceiling opening 510
Hanging bolt pitch
410
View A
Minimum
600
Minimum
600
Minimum
600
Space required for service and installation
(All dimensions in mm)