EasyManua.ls Logo

Toshiba HFCR407C - Refrigeration cycle schematic; Indoor units

Toshiba HFCR407C
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
Refrigeration cycle schematic
Indoor units
Model (A)
mm Capillary (B) Inner
mm (C)
mm PMV code (D)
BUILT-IN DUCT MM-B 056 6.4 1.7 x 150L x 3 12.7 40
080 9.5 2.6 x 200L x 4, 2.6 x 400L x 2 15.9 40
112 9.5 2.0 x 400L x 6 19.0 40
140 9.5 2.2 x 200L x 6 19.0 60
CEILING MM-C 042 6.4 3.0 x 100L x 3 12.7 25
MM-CR 056 6.4 3.0 x 100L x 3 12.7 40
080 9.5 3.0 x 100L x 5 15.9 40
112 9.5 3.0 x 200L x 7 19.0 40
140 9.5 3.0 x 200L x 7 19.0 60
HIGH WALL MM-K 042 6.4 3.0 x 100L x 3 12.7 25
MM-KR 056 6.4 3.0 x 100L x 3 12.7 40
080 9.5 3.0 x 100L x 5, 3.0 x 200L x 1 15.9 40
CHASSIS MM-N 028 6.4 1.7 x 250L x 2 12.7 25
042 6.4 3.0 x 200L x 2 12.7 25
056 6.4 3.0 x 100L x 4 12.7 40
080 9.5 3.0 x 200L x 6 15.9 40
LOW WALL MM-S 056 6.4 3.0 x 100L x 3 12.7 40
MM-SR 080 9.5 3.0 x 100L x 6 15.9 40
BUILT-IN SLIM DUCT MM-SB 028 6.4 1.7 x 250L x 2 12.7 25
2-WAY CASSETTE MM-TU 028 6.4 3.0 x 100L x 2 12.7 25
042 6.4 2.4 x 300L x 2 12.7 25
056 6.4 3.0 x 100L x 2 12.7 40
4-WAY CASSETTE MM-U 056 6.4 2.0 x 200L x 3 12.7 40
080 9.5 2.6 x (150L x 2), (200L x 3), (400L x 1) 15.9 40
112 9.5 2.6 x (200L x 6), (300L x 2), (500L x 2) 19.0 40
140 9.5 2.6 x (200L x 6), (300L x 2), (500L x 2) 19.0 60
10
Liquid
sensor
Distributor
strainer
Capillary
tube (B)
Heat exchanger
Gas
sensor
Check
joint
Pressure
sensor
Strainer
Refrigerant pipe
(gas) (C)
Refrigerant pipe
(liquid) (A)
PMV (D)
TC2
TC1
Strainer

Table of Contents

Related product manuals