Self diagnostic display information
Outdoor units
Outdoor unit information data display (Displayed on each outdoor unit)
SW03 SW02 SW01 Displayed content
1 1 1 Check code A [U1] to [U5]: Outdoor unit number (1 = Inverter)
B [—]: Normal time (No error)
A check code is displayed in abnormality
<SW04>: Push function:
Only fan of unit in which an error occurred operates.
<SW04> and
<SW05>: Push function: Only fan of normal unit operates.
<SW05>: Push function: Fan operation function is interrupted.
2 Type of installed compressor A [U1] to [U2]: Outdoor unit number
B [A]: Fixed-speed 2 in 1; [b]: Fixed-speed 2 compressor
[C]: Fixed-speed single, [d] Inverter (2 in 1)
3 Operation mode A
B [C]: Cooling operation, [H]: Heating operation
4 Outdoor unit capacity A [6], [8], [10]: 6, 8, 10 HP
B[HP]
5 Compressor operation command A [1.-]: No. 1 compressor stop status, [1.1]: During operation
For inverter, the frequency code is displayed: [00] to [FF]
B [2.-]: No. 2 compressor stop status, [2.1]: During operation
<SW04>: Push function: Inverter frequency data is displayed in decimal notation.
<SW05>: Push function: Release of frequency data display in decimal notation.
6 Outdoor fan operation pattern A [FP]
B [0] to [16]: 0 wave (stop) to 16 waves (All waves)
7 Compressor back-up A [C1]: Under No. 1 compressor back-up set-up
B [C2]: Under No. 2 compressor back-up set-up
8— A
B—
9 Control valve output AB
SV2: OFF H. O 2. 0
SV2: ON H. O 2. 1
10 SV3A: ON/SV3B: OFF/SV3C: OFF 3. 1 0 0
SV3A: OFF/SV3B: ON/SV3C: OFF 3. 0 1 0
SV3A: OFF/SV3B: OFF/SV3C: ON 3. 0 0 1
11 SV41: ON/SV42: OFF 4. 0 1 0
SV41: OFF/SV42: ON 4. 0 0 1
12
13
14 PMV A1 + PMV A2 opening [00] to [500]: 0 to 1000 pulse 0 0 P
15 PMVB opening [00] to [500]: 0 to 500 pulse 0 0 P
16 Oil level judgement status A [OL]
B [ ]: Initial display, [FF]: Oil judgement start status,
[AO]: Adequate,[A1]: Shortage,[ A2 to A4]: Detection error
<SW04>: Push function: Oil level judgement control forcible start
(Detection starts after timer countdown)
<SW05>: Push function: Oil level shortage status/continuous counter display
(Displayed for several seconds)
NOTE: The push-switch function operates by input from the inverter unit.