Control circuit configuration
Indoor units
(5) Contents of switch set-up
Network address set-up table by DIP switch (SW02)
• After turning off the power source, set 7 of DIP switch (SW02) to ON.
Address set-up from the remote controller becomes unavailable.
Address No. DIP switch (SW02)
123456
33 XXXXXO
34 OXXXXO
35 XOXXXO
36 OOX X XO
37 XXOXXO
38 OX OX XO
39 X OOX XO
40 OOOX X O
41 XXXOXO
42 OXXOXO
43 XOXOXO
44 OOX OX O
45 XXOOXO
46 OX OOX O
47 X OOOX O
48 OOOOXO
49 XXXXOO
50 OXXXOO
51 XOXXOO
52 OOX X OO
53 XXOXOO
54 OX OX OO
55 X OOX OO
56 OOOX OO
57 XXXOOO
58 OXXOOO
59 XOXOOO
60 OOX OOO
61 XXOOOO
62 OX OOOO
63 X OOOOO
64 OOOOOO
Address No. DIP switch (SW02)
123456
1 XXXXXX
2 OXXXXX
3XOXXXX
4 OOXX X X
5 XXOXXX
6OXOXXX
7 XOOX X X
8 OOOX XX
9 XXXOXX
10 OXXOXX
11 XOXOXX
12 OOX OX X
13 XXOOXX
14 OX OOX X
15 X OOOX X
16 OOOOXX
17 XXXXOX
18 OXXXOX
19 XOXXOX
20 OOX X OX
21 XXOXOX
22 OX OX OX
23 X OOX OX
24 OOOX OX
25 XXXOOX
26 OXXOOX
27 XOXOOX
28 OOX OOX
29 XXOOOX
30 OX OOOX
31 X OOOOX
32 OOOOOX
SW08 Selected content
1234
X X O X Indoor capacity: 0.8 HP
X X O O Indoor capacity: 1.0 HP
X O X X Indoor capacity: 1.25 HP
X O X O Indoor capacity: 1.5 HP
X O O X Indoor capacity: 1.7 HP
X O O O Indoor capacity: 2.0 HP
O X X X Indoor capacity: 2.5 HP
O X X O Indoor capacity: 3.0 HP
O X O X Indoor capacity: 3.2 HP
O X O O Indoor capacity: 4.0 HP
O O X X Indoor capacity: 5.0 HP
NOTE:
O : ON X: OFF (Numeral) side
DIP switch table for indoor unit HP set-up.