28
Function Code Setting
Function Code
Range Default
Setting Address
Hydro
Unit
Remote
Controller
(5) Anti Bacteria
Setting Temperature (°C) 0A - 70~80°C 75
Start Cycle (Day) - 0D 1~10 7
Start Time (Hour) - 0C 0~23 22
Operation Time (min) 0B - 0~60 30
(7) Heating Auto Curve
Settings
Outside Temperature T1 (°C) 29 - -15~0°C -10
Outside Temperature T2 (°C) - - 0 0
Outside Temperature T3 (°C) 2B - 0~15°C 10
Setting Temperature A @ OAT -20°C (°C) 2C - 20~55°C 40
Setting Temperature B @ OAT T1 (°C) 2D - 20~55°C 35
Setting Temperature C @ OAT T2 (°C) 2E - 20~55°C 30
Setting Temperature D @ OAT T3 (°C) 2F - 20~55°C 25
Setting Temperature E @ OAT 20°C (°C) 30 - 20~55°C 20
Ratio Of Zone 2 In Zone 1 Auto Mode (%) 31 - 0~100% 80
Auto Curve - Temperature Shift (°C) 27 - -5~5°C 0
(8) Frost Protection
Function 0=Invalid; 1=Valid 3A - 0~1 1
Frost Protection Setting Temperature (°C) 3B - 10~20°C 15
Frost Protection – Schedule End Day - 12 0~20 0
Frost Protection – Schedule End Time - 13 0~23 0
(9) Back Up Heater
Control
Downtime Back Up Heater 0=5min;
1=10min;2=15min;3=20min
33 - 0~3 1
Uptime Back Up Heater 0=10min; 1=20min;
2=30min; 3=40min
34 - 0~3 0
(10) Night Setback
Change Setback Temperature 26 - 3~20°C 5
Zone selection 0=Zone 1 & 2; 1= Zone 1 Only 58 - 0~1 1
Start Time (Hour) - 0E 0~23 22
End Time (Hour) - 0F 0~23 06
(11) Room temperature
Remote Controller
Room Temperature Control:
0 = Invalid; 1 = valid
40 - 0~1 0
Setting Room Temperature Range:
Cooling room temperature upper limit (°C)
92 - 15~30 29
Setting Room Temperature Range:
Cooling room temperature lower limit (°C)
93 - 15~30 18
Setting Room Temperature Range:
Heating room temperature upper limit (°C)
94 - 15~30 29
Setting Room Temperature Range:
Heating room temperature lower limit (°C)
95 - 15~30 18
Room Temperature Offset:
Heating room temperature offset value (sensor
temperature – control temperature °C)
- 02 -10~10 -1
Room Temperature Offset:
Cooling room temperature offset value (sensor
temperature – control temperature °C)
- 03 -10~10 -1
Initial Target Water Temperature – Cooling:
Room temperature controller or external room
thermostat (°C)
96 - 10~25 20
Initial Target Water Temperature – Heating:
Room temperature controller or external room
thermostat (°C)
9D - 20~55 40