Toshiba HWS-1403XWHT6-E - Start up and Configuration

Toshiba HWS-1403XWHT6-E
179 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
To control room temperature instead of water
temperature with this remote control, set function
code “40” of hydro unit to “1”.
8 START UP AND CONFIGURATION
Set the DIP switches and function codes.
Setting DIP Switches on the Board in the Hydro Unit
Detach the front cover and the electric parts box cover of the Hydro Unit.
Set the DIP switches on the main board.
ON
OFF
SW10 SW11 SW12 SW13
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
Fig. 8-01
SW No. DIP No. Description Default
After
Commissioning
Change 1 Change 2 Change 3
02
1
Boiler install position
OFF = Heating side after 3 way valve
ON = Before 3 way valve
OFF
2 Not Used
3 Not Used
4
Used to when an external room thermostat is
connected
OFF = No external room thermostat;
ON = External room thermostat connected
OFF
10
1
P1 Pump operation for hot water
OFF = synchronised with heat pump
ON = Normally run
OFF
2
P1 Pump operation for heating
OFF = Normally run
ON = Stopped at the outside temperature over 20°C
OFF
3
Synchronisation of Pump P2.
OFF = P2 continuous operation (pump off when
remote controller switched off)
ON = P1 synchronised with pump P1
OFF
4 Not Used
11
1
Used to activate Hydro Unit back up heaters.
OFF = Back up heaters activated;
ON = back up heaters de-activated
OFF
2
Used to activate hot water cylinder electrical heater.
OFF = hot water cylinder heater activated;
ON = hot water cylinder heater de-activated
OFF
3
Used to activate external booster heater output.
OFF = external booster heater output activated;
ON = external booster heater output de-activated
OFF
4 Not Used