5.OUTDOOR UNIT
Engineering Data book
61
Outdoor unit
HWS-1103H8-E
HWS-1103H8R-E
HWS-1403H8-E
HWS-1403H8R-E
HWS-1603H8-E
HWS-1603H8R-E
Power supply 3N ~ 380-400V 50Hz
Compressor
Type Twin rotary type with DC-Inverter variable speed control
Motor Output kW 3.75
Pole 4
Refrigerant charged 2.7
Refrigerant control Pulse motor valve
Pipe length
Minimum m5
Maximum m30
Height difference Outdoor-Hydro unit m30
Appearance
Color Silky shade (Muncel 1Y8.5-0.5)
Material PCM
Outer dimension
Height mm 1340
Width mm 900
Depth mm 320
Unit weight kg 93
Packing
dimension
Height mm 1425
Width mm 971
Depth mm 436
Total weight unit and packing kg 100
Heat exchanger Type Finned tube
Fan unit
Fan Propeller fan
Standard air flow m
3
/min 101 103
Motor W 100+100
Bottom plate heater W–––
Sound pressure
level
Heating normal dBA495152
Heating low noise* dBA444444
Cooling normal dBA505152
Cooling low noise* dBA454545
Hot water normal dBA495152
Hot water low noise dBA444444
Operation
outdoor temp
Heating °C -20 to 25
Cooling °C 10 to 43
Hot water °C -20 to 43
Refrigerant pipe
Gas mm 15.9
Liquid mm 9.5