–35–
EN
Hydro Unit
Installation Manual
Function code settings
Location & FC
Number
FC Description Hydro RC Range Default
After
Commissioning
Change
1
Change
2
1
Setting
Temperature
Range
Heating Upper Limit - Zone 1 1A 37~55°C 55°C
Heating Lower Limit - Zone 1 1B 20~37°C 20
Heating Upper Limit - Zone 2 1C 37~55°C 55
Heating Lower Limit - Zone 2 1D 20~37°C 20
Cooling - Upper Limit 18 18~30°C 25
Cooling - Lower Limit 19 10~20°C 10
Hot Water - Upper limit 1E 60~75°C 75
Hot Water - Lower limit 1F 40~60°C 40
2
Hot Water
Operation
Heat Pump Start Temperature 20 20~45°C 38
Heat Pump Stop Temperature 21 40~50°C 45
3
Hot Water
Temperature
Compensation
Temperature Compensation
Outside Air Temperature (°C)
24 -20~10°C 0
Compensation Temperature
(°C)
25 0~15°C 3
4 Hot Water Boost
Operation Time (x10 min) 08 3~18 6
Setting Temperature (°C) 09 40~75°C 75
5 Anti Bacteria
Setting Temperature (°C) 0A 65~75°C 75
Start Cycle (Day) 0D 1~10 7
Start Time (Hour) 0C 0~23 22
Operation Time (min) 0B 0~60 30
6 Priority Mode
Hot Water & Heating
Switching Temperature (°C)
22 -20~20 0
Boiler & Heat Pump Switching
Temperature (°C)
23 -20~20 -10
7
Heating Auto
Curve Settings
Outside Temperature T1 (°C) 29 -15~0°C -10
Outside Temperature T2 (°C) 0 0
Outside Temperature T3 (°C) 2B 0~15°C 10
Setting Temperature A @ OAT
-20°C (°C)
2C 20~55°C 40
Setting Temperature B @ OAT
T1 (°C)
2D 20~55°C 35
Setting Temperature C @
OAT T2 (°C)
2E 20~55°C 30
Setting Temperature D @
OAT T3 (°C)
2F 20~55°C 25
Setting Temperature E @ OAT
20°C (°C)
30 20~55°C 20
Ratio Of Zone 2 In Zone 1 Auto
Mode (%)
31 0~100% 80
Auto Curve - Temperature
Shift (°C)
27 -5~5°C 0
8 Frost Protection
Function 0=Invalid; 1=Valid 3A 0~1 1
Frost Protection Setting
Temperature (°C)
3B 10~20°C 15
Schedule date 12 0~99 0
Schedule time 13 0~23 0
9
Back Up Heater
Control
Downtime Back Up Heater
0=5min;
1=10min;2=15min;3=20min
33 0~3 1
Uptime Back Up Heater
0=10min; 1=20min; 2=30min;
3=40min
34 0~3 0