EasyManua.ls Logo

Toshiba HWS-802XWHM3-E - Page 30

Toshiba HWS-802XWHM3-E
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.HYDRO UNIT
Engineering Data book
29
Cooling capacity and power input
* Cooling capacity and power input are the data at rated compressor operating frequency of rated condition 1
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 7.36 8.05 8.81 9.25 10.03
27 6.76 7.39 8.09 8.49 9.21
30 6.46 7.06 7.73 8.12 8.80
35 6.00 6.56 7.18 7.54 8.18
40 5.50 6.01 6.58 6.91 7.49
43 4.62 5.00 5.44 5.69 6.09
Power input (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 1.60 1.63 1.66 1.68 1.70
27 1.84 1.86 1.90 1.92 1.95
30 1.90 1.93 1.97 2.00 2.02
35 2.13 2.16 2.20 2.23 2.26
40 2.30 2.34 2.38 2.41 2.44
43 2.09 2.09 2.09 2.09 2.09
EER
LWT (°C)
7 10 13 15 18
TO
(°C)
20 4.60 4.95 5.32 5.51 5.91
27 3.68 3.97 4.26 4.41 4.73
30 3.39 3.65 3.92 4.07 4.36
35 2.82 3.04 3.26 3.38 3.62
40 2.39 2.57 2.76 2.86 3.07
43 2.21 2.40 2.60 2.72 2.91
TO : Outdoor temperature (DB°C)
LWT : Leaving water temperature (°C)

Table of Contents

Other manuals for Toshiba HWS-802XWHM3-E

Related product manuals