4.HYDRO UNIT
Engineering Data book
30
4
Heating capacity and input specifications
▼Outdoor unit HWS-1102H-E
Hydro unit HWS-1402XWH**-E
Rated heating capacity and power input
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
Rated condition 1
TO (DB/WB)=7/6°C
LWT=35°C
dT=5deg
Capacity kW 11.2
Power input kW 2.4
COP W/W 4.66
Rated water flow rate /min 32.1
Rated condition 2
TO (DB/WB)=7/6°C
LWT=45°C
dT=5deg
Capacity kW 11.2
Power input kW 2.95
COP W/W 3.80
Rated water flow rate /min 32.1
TO : Outdoor temperature (DB°C) RH85%
LWT : Leaving water temperature (°C)
dT : Delta temperature (deg)
Leaving water temperature - return water temperature