4.HYDRO UNIT
Engineering Data book
33
▼Outdoor unit HWS-1102H-E
Hydro unit HWS-1402XWH**-E
Rated cooling capacity and power input
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Rated condition 1
TO=35°C
LWT=7°C
dT=5deg
Capacity kW 10.0
Power input kW 3.52
EER W/W 2.84
Rated water flow rate /min 28.7
Rated condition 2
TO=35°C
LWT=18°C
dT=5deg
Capacity kW 10
Power input kW 2.35
EER W/W 4.26
Rated water flow rate /min 28.7
TO : Outdoor temperature (DB°C)
LWT : Leaving water temperature (°C)
dT : Delta temperature (deg)
Return water temperature - Leaving water temperature