4.HYDRO UNIT
Engineering Data book
34
4
Cooling capacity and power input
* Cooling capacity and power input are include are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 12.78 13.64 14.99 16.03 16.98
27 11.60 12.38 13.61 14.55 15.42
30 11.03 11.77 12.94 13.83 14.66
35 10.00 10.67 11.73 12.54 13.29
40 8.96 9.56 10.51 11.24 11.91
43 6.89 7.35 8.08 8.64 9.16
Power input (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 2.64 2.70 2.74 2.77 2.78
27 3.04 3.11 3.16 3.18 3.20
30 3.23 3.30 3.35 3.38 3.40
35 3.52 3.59 3.65 3.68 3.70
40 3.82 3.84 3.86 3.88 3.91
43 3.28 3.28 3.28 3.29 3.29
EER
LWT (°C)
7 10 13 15 18
TO
(°C)
20 4.83 5.05 5.47 5.80 6.11
27 3.81 3.98 4.31 4.57 4.81
30 3.41 3.57 3.86 4.09 4.31
35 2.84 2.97 3.21 3.41 3.59
40 2.34 2.49 2.72 2.90 3.04
43 2.10 2.24 2.46 2.62 2.78
TO : Outdoor temperature (DB°C)
LWT : Leaving water temperature (°C)