4.HYDRO UNIT
Engineering Data book
35
▼Outdoor unit HWS-1402H-E
Hydro unit HWS-1402XWH**-E
Rated heating capacity and power input
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
Rated condition 1
TO (DB/WB)=7/6°C
LWT=35°C
dT=5deg
Capacity kW 14.0
Power input kW 3.15
COP W/W 4.45
Rated water flow rate /min 40.1
Rated condition 2
TO (DB/WB)=7/6°C
LWT=45°C
dT=5deg
Capacity kW 14.0
Power input kW 3.95
COP W/W 3.54
Rated water flow rate /min 40.1
TO : Outdoor temperature (DB°C) RH85%
LWT : Leaving water temperature (°C)
dT : Delta temperature (deg)
Leaving water temperature - return water temperature