–86–
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the
electrical box.
Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.
Electrical connection for external booster heater
CAUTION
The maximum current available from the booster heater output is 1 A. Do not connect the booster
pump directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied locally, must
be used to supply the booster heater.
The booster heater can be installed only for room heating and cannot be used for hot water supply.
Install the booster heater downstream of the 3-way valve on the indoor unit side.
The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during low ambient
conditions.
The AC230
V 1 A output from the Hydro Unit must only be used to energize an external contactor. (Supplied locally)
The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -10°C.
Ensure the external booster heater is installed and set up in accordance with all Local, National and International
regulations.
Connect the external booster heater to the Hydro Unit in accordance with the diagram shown below.
Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The contactor will
energize in the event of low ambient conditions.
A separate dedicated electrical supply must be used for the external booster heater. This must be connected
through the contacts on the field supplied contactor.
Electrical connection for external additional pumps
The Hydro Unit has the facility to connect an additional circulating pump, if required, into the heating or cooling
system.
There is an output available from the Hydro Unit. AC230 V 1 A (maximum) is available from each output. The
output for each additional pump is synchronized with the operation of the main circulating pump inside the Hydro
Unit.
Connect the additional pumps as shown in the diagram below.
Connect external pump 1 to terminals 1 & 2 on Terminal Block 05.
Install external pumps so that their motive power does not affect the internal pump.
1234567 8 9
Fig. 7-23
Terminal Block 05
Booster Heater
1234567 8 9
01
Fig. 7-24
Terminal Block 05
Pump
24-EN