–88–
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system.
Connect the 3-way mixing valve to terminals 2, 3 and 4 on Terminal Block 04 (for Type 1 mixing valve) or on
terminals 1, 2 and 3 on Terminal Block 04 (for Type 2 mixing valve).
Connect the 3-way mixing valve in accordance with the diagrams below:-
Hot water cylinder connection (optional)
Please refer to “Electrical supply/cable specifications” for fuse/cable size and for connection details.
Electrical Connection (Hot Water Cylinder Electric Heater)
The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro Unit.
Connect the hot water cylinder heater electrical supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 03
Neutral conductor: Terminal N on Terminal Block 03
Earth Conductor: Earth terminal on Terminal Block 03
Connect the hot water cylinder heater to the Hydro Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03
Electrical Connection (Hot Water Cylinder temperature Sensor)
Connect the hot water cylinder temperature sensor as shown below to terminals A & B on Terminal Block 06 in
the Hydro Unit.
Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder, is connected
to earth at both ends of the cable using the shield wire.
Fig. 7-28
2
1
3
4
Fig. 7-29
Type 1: SPDT Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
port “B” BLANK OFF
port “A”
close
open
2
1
3
4
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
TB 04
Hydro Unit
TB 04
12 LN
1
2
Fig. 7-30
Earth leakage breaker
INPUT Power 230 V ~ 50 Hz
Terminal block 03
Hot water cylinder
26-EN