Hydro Unit
Installation Manual
10 Night Setback
Change Setback Temperature 26 – 3~20°C 5
Zone selection 0=Zone 1 & 2;
1= Zone 1 Only
58 – 0~1 1
Start Time (Hour) – 0E 0~23 22
End Time (Hour) – 0F 0~23 06
11
Room
Temperature
control Setting
Compensating Temperature 35 – 1~5°C 1
Downtime zone B (x5min) 36 – 1~24 6
Uptimezone C (x5min) 37 – 1~24 6
Cooling upper limit 92 – 0~55 29
Cooling lower limit 93 – 0~55 18
Heating upper limit 94 – 0~55 29
Heating lower limit 95 – 0~55 18
Target water temperature in
cooling mode
96 – 10~30 20
Target water temperature in
heating mode
9D – 20~55 40
12
Hydro 2 Way
Valve Operation
Control
Cooling 2 Way Valve -
Operation Logic 0=Activated
during cooling; 1=Not
activated during cooling
3C – 0~1 0
13
Hydro 3 Way
Diverting Valve
Operation Control
3 Way Diverting Valve
Operation Logic 0=Activated
during hot water operation;
1=not activated during hot
water operation
54 – 0~1 0
14
2 Zone Mixing
Valve Drive Time
Specified Drive Time for
Mixing Valve (x10sec)
0C – 3~24 6
Mixing valve OFF (control time
- mins)
59 – 1~30 4
15
Boiler/Heat Pump
Synchronisation
External Boiler/Heat Pump
Synchronisation
0=Synchronised; 1=Not
synchronised
3E – 0~1 0
16
Maximum
Operation Time Of
Hot Water Heat
Pump
Maximum Heat Pump
Operation Time In Hot Water
Operation Priority Mode
(minutes)
07 – 1~120 30
17 Cooling Operation
0=Cooloing & Heating
Operation; 1=Heating Only
Operation
02 – 0~1 1
18
Remote Controller
Indication
24h or 12h Time Indication 0=
24h; 1=12h
–050~10
19
CDU Night Time
Low Noise
Operation
Low Noise Operation
0=Invalid; 1=Valid
–090~10
Start Time (Hour) – 0A 0~23 22
End Time (Hour) – 0B 0~23 06
20 Alarm Tone Tone Switching 0=OFF; 1=ON – 11 0~1 1
Location & FC
Number
FC Description Hydro RC Range Default
After
Commissioning
Change
1
Change
2