7.10.2 PV ECO operation in BOOST mode
When the photovoltaic mode is set to PV ECO and the DHW-HP mode is set to BOOST, there is no
operation of the electrical heater, even if the 0~10V input rises above the D21 (PV Min Voltage EL)
set point.
0~10V input raised until >8V, set from D20 (PV Min Voltage HP) & D21(PV Min Voltage EL)
HP starts after 5 minutes delay, set from D22 (PV Min Time). Electric heater does not start due to
PV ECO mode being selected.
0~10V input decreased until <5V, set from D20 (PV Min Voltage HP)
HP stops after 5 minutes delay, set from D22 (PV Min Time)
Note: If water set point temperature is achieved then the heat pump stops operation.