Domestic Hot Water Heat Pump Service Manual
45
9.2 In the event of an error – how to operate BACK-UP mode
In the event of an error occurring it is possible to produce domestic hot water by operating the
DHW-HP in Back-Up mode, for more information see section 7.4.
If Yes is selected the unit operates at the lower set point set by D12 (BACK-UP Temp)
Note: The Back-up mode uses the electric heater only to heat a smaller volume of water to set
point. In the 190l tank this is 80l and in the 260l tank this is 130l.
The water temperature at which the unit stops the backup mode with only
the electric heater.
9.3 Error codes
The following error codes are shown on the remote controller LCD screen at the time of a fault.
The temperature sensor BT1 is out of range
The temperature sensor BT2 is out of range
The temperature sensor BT3 is out of range. If BT3 Error occurs, the unit does not heat the
water in any way
The temperature sensor BT4 is out of range. The error Er4 is ignored and the unit runs normally
The temperature sensor BT5 is out of range. The error Er5 is ignored and the unit runs normally
The pressure switch opens, when the pressure in the heating circuit is above the limit of
pressure specified on the high pressure switch
The temperature sensor BT2 is above BT1 - 2°C for more than one hour
The temperature BT2 is below - 25°C
The temperature BT2 is above D11 (Evaporator T max)
Replace filter. The alarm is displayed on the main screen, but the operation of the unit is not
affected.
Alarm Meaning Possible reasons Possible solutions
Temperature sensors out
of range
The temperature sensor BT1, BT2, BT3, BT4 or BT5
is defective or not connected to the PCB
Check that the sensor is connected to the PCB
Substitute the temperature sensor
High pressure in the heating system
Reduce the water temperature set point
Reduce the fan maximum speed in the installer
menu
High pressure switch BP1 is defective or not
connected to the PCB
Er 7 - Err
Evap /
Er9 - Err
H Evap
High evaporator
temperature
Wrong position of the temperature sensor
Check that BT2 is positioned in the evaporator
Fix leakages and charge refrigerant
Low evaporation
temperature
Make sure that the fan is connected to the PCB or
substitute the component
Increase the minimum fan speed in the installer
menu
Low air inlet temperature BT1
Increase the minimum air temperature in the
installer menu
Substitute the air filter