144
15. Floor drying
This function is available only for the header remote controller.
This function is used for drying concrete etc.
Service personnel must operate the unit after setting the related function code.
Operation is not started unless All the related function codes are set.
Refer to the following for the settings of the related items. Please setup on the responsibility for an installer. An
unsuitable setup may cause a crack of concrete etc.
When the operation starts, the unit operates as follows.
1 Press the [ ] button and the [ ] button at same time for 4
seconds or longer on the top screen to display the “FIELD SETTING
MENU”.
2 Press the [ ] / [ ] button to select "Floor drying" on the
FIELD SETTING MENU, then press the [ ] button for 4 seconds or
longer.
FC:14 setting start and End temperature [20-55°C]
FC:15 setting Max temperature [20-55°C]
FC:16 continuation days for every step up to Max temperature [1-7 days]
FC:17 temperature difference for every step up to Max temperature [1-10 K]
FC:18 continuation days for every step down to End temperature [1-7 days]
FC:19 temperature difference for every step down to End temperature [1-10 K]
FC:1A Continuation days in Max temperature [1-30 days]
3 Press the [ ] / [ ] button to select FC number or Data, then press
the [ ] / [ ] button to set the value.
4 Press the [ ] button. The set value is registered.
Test mode
FIELD SETTING MENU(1/2)
Floor drying
Forced defrosting
Information input
Alarm history
SET
FC:14
FC:15
FC:16
°C
50
49
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
:
:
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Day
FC:17
FC:1A
FC:19
FC:18
lapsed days
setting temperature
total days
Floor drying
FC No. Data
FIX

Table of Contents