154
11Replacement of the service PC board
Setting the jumper wires and DIP switches
Model switching (J800 to J803)
Since this service PC board is available for several models, cut the jumper wires according to the following table.
If they are not cut correctly, an error code “L10” or “L29” appears on the remote controller and the operation of the
air conditioner is disabled.
Outdoor unit Service Parts (CDB)
HWS-P805HR-E, P1105HR-E 3026V053 (MCC-1571)
Parts name Function Setting
Jumper wire J800~J803 Model switching Cut these jumper wires according to the following table.
J804~J811 Settings Set these jumper wires to the settings of the PC board
before replacement.
DIP switch SW802 Settings Set SW802 to the setting of the PC board before
replacement.
SW803 LED indication switching Set SW803 to all OFF.
SW804 Special operations for
service
Set SW804 to all OFF.
SW805 (Only H8series) Special operations for
service
Set SW805 to all OFF
Model name J 800 J 801 J 802 J 803
Factory default
HWS-805H-E
HWS-1105H-E
HWS-1405H-E
HWS-P805HR-E
HWS-P1105HR-E
* : Characters that indicate the following:
No character -- Standard models
R ----- For with cord heater
:Connected, :Cut
<HWS-P805HR-E, P1105HR-E>
SW802
SW804
J800-J803
SW803
MCC-1571

Table of Contents