2-2. How to set remote controller DN
<Procedure> Perform the following when no operation is in progress.
1 Press the [ ] button and the [
] button at same time for 4
seconds or longer on the top screen to display the “FIELD SETTING
MENU”.
2 Press the [
] / [
]button to select “Remote controller DN”
on the FIELD SETTING MENU screen, then press the [
] button.
3 Press the [
] / [
] button to select DN or Data, then press the
[
] / [
] button to set the value.
4 Press the [ ] button. The set value is registered.
Data
0071
01
SET