2 Replacement of service main PC board
WARNING
NOTE
NOTE
2
2E30099003
❐1 Readout of the setup data from the memory
Readout of the Memory (factory setup data and customer setup data)
1. Press the [ ] button and the [ ] button at same time for at least 4 sec.
“FIELD SETTING MENU” will be displayed on the top of the screen.
2. Press the [ ] / [ ] button to select “Hydro Unit DN” on the
“FIELD SETTING MENU” screen, then press the [ ] button.
3. Using the [ ] / [ ] button,
the DN code Number can be increased or decreased one by one.
Make a note of the setup data displayed in this step.
4. Repeat item 3. and make a note of the setup data as shown in the later table.
5. Press the [ ] button to return the status to usual stop status.
(Approx. 1 minute is required to start up of the remote controller.)