DN table
DN Item Details Factory default
02 Cooling/Non-cooling switching 0000: Cooling 0001: Not cooling 0000: Cooling
03 Central control address 0001 - 0128 None
08 Hot water boost operation time (operating time) 0003: 30 min - 0018: 180 min 0006: 60 min
09 Hot water boost set temperature 0040: 40°C - 0080: 80°C 0075: 75°C
0A Anti bacteria set temperature 0065: 65°C - 0080: 80°C 0075: 75°C
0B Anti bacteria holding time 0000: 0 min - 0060: 60 min 0030: 30 min
0C Mixing valve drive time 0003: 30 sec - 0024: 240 sec 0006: 60 sec
0F Hot water HP allowance while cooling + hot water
supply
0000: Not allow - 0001: Allow 0000: Not allow
10 Type setting 0070: Wall mounted type
0071: AIO type
Depend on type
11 Water heat exchanger capacity 0010: 601 0015: 1101 Depend on type
12 Line address 0001 - 0128 None
13 Indoor address 0001 - 0128 None
14 Group address 0000: Individual (Not group control)
0001: Header unit
0002: Follower unit
None
18 Upper limit of cooling set temperature 0018: 18°C - 0030: 30°C 0025: 25°C
19 Lower limit of cooling set temperature 0007: 7°C - 0020: 20°C 0007: 7°C
1A Upper limit of heating (ZONE1) set temperature 0037: 37°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0055: 55°C (401 / 601)
0065: 65°C (801 / 1101)
1B Lower limit of heating (ZONE1) set temperature 0020: 20°C - 0037: 37°C 0020: 20°C
1C Upper limit of heating (ZONE2) set temperature 0037: 37°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0055: 55°C (401 / 601)
0065: 65°C (801 / 1101)
1D Lower limit of heating (ZONE2) set temperature 0020: 20°C - 0037: 37°C 0020: 20°C
1E Upper limit of hot water set temperature 0060: 60°C - 0080: 80°C 0075: 75°C
1F Lower limit of hot water set temperature 0040: 40°C - 0060: 60°C 0040: 40°C
20 Hot water HP start temperature 0020: 20°C - 0045: 45°C 0038: 38°C
21 Hot water HP stop temperature 0040: 40°C - 0065: 65°C 0052: 52°C
22 Priority mode Hot water supply/Heating switching
temperature
-0040: -40°C - 0020: 20°C 0000: 0°C
23 Boiler output enable switching temperature -0020: -20°C - 0020: 20°C -0010: -10°C
24 Outside air temperature for hot water temperature
compensation start
-0020: -20°C - 0010: 10°C 0000: 0°C
25 Hot water temperature compensation value 0000: 0K - 0015: 15K 0003: 3K
26 Night setback change temperature range 0003: 3K - 0020: 20K 0005: 5K
27 Set temperature shift with heating Auto -0005: -5K - 0005: 5K 0000: 0K
28 Auto Restart of power outage after system power
failure
0000: No 0001: Yes 0001: Yes
29 Outside air temperature T1 temperature -0015: -15°C - 0000: 0°C -0010: -10°C
2B Outside air temperature T3 temperature 0000: 0°C - 0015: 15°C 0010: 10°C
2C Set temperature A with outside air temperature of T0 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0040: 40°C
2D Set temperature B with outside air temperature of T1 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0035: 35°C
2E Set temperature C with outside air temperature of 0°C 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0030: 30°C
2F Set temperature D with outside air temperature of T3 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0025: 25°C
30 Set temperature E with outside air temperature of 20°C 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0020: 20°C
31 Zone2 ratio with Zone1 as Auto 0000: 0% - 0100: 100% 0080: 80%
33 Hydro unit backup heater down time 0000: 5 min
0002: 15 min
0001: 10 min
0003: 20 min
0001: 10 min
* DN_11, 6B8, 6BA, 6BC are needed for PCB replacement or DN code reset procedure has been completed.