144
2-2. How to set remote controller DN
<Procedure> Perform the following when no operation is in progress.
1 Press the [ ] button and the [ ] button at same time for 4
seconds or longer on the top screen to display the “FIELD SETTING
MENU”.
2 Press the [ ] / [ ] button to select “Remote controller DN”
on the FIELD SETTING MENU screen, then press the [ ] button.
3 Press the [ ] / [ ] button to select DN or Data, then press the
[ ] / [ ] button to set the value.
4 Press the [ ] button. The set value is registered.
FIELD SETTING MENU(2/2)
SET
Service monitor
Hydro Unit DN
Remote controller DN
Reset power consumption data
Sensor information
01
Remote controller DN
(DN) Data
FIX
0000
e
d
oC