147
A4 Set temperature B' with outside temperature of T1 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0035: 35°C
A5
Set temperature E' with outside temperature of 20°C
0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0020: 20°C
AB Group control 0000: TTW value of each Hydro Unit
0001: TTW value transmitted from Master Unit
0000: each Hydro Unit
AC The temperature increase during
“Forced ON” mode (SG Ready control)
0-10 (0K - 10K) 0000: 0K
B2 HP restart water temperature in A zone. (Valid only
room temp control using 2nd remote controller)
0020: 20°C 0037: 37°C 0025: 25°C
B5 Initial water temperature setting method when
controlling heating by the room temperature remote
controller and room temperature thermostat
0000: The fixed temperature by DN_9D
0001: The calculated temperature by Auto curve
0000: The fixed
B6 Setting the objects to control of I/P 7, 8 0000: I/P 7 Emergency shutdown input, I/P 8 None
0001: I/P 7 TEMPO 1 input, I/P 8 None
0002: I/P 7 TEMPO 2 input, I/P 8 None
0003: I/P 7 Forcibly turn off the backup heater,
I/P 8 Forcibly turn off the hot water tank heater
0004: I/P 7 SG network input 1,
I/P 8 SG network input 2
0000: I/P 7
Emergency
shutdown input,
I/P 8
None
B8 Forcibly heater off at T0 ≥ A°C 0000: no restriction, 0001: 20°C
0002: 15°C, ···, 0006: -5°C
0000: no restriction
B9 Backup heater energization temperature during
defrosting.
Correction coefficient B
0000: 0K, ···, 0004: 40K
0000: 0K
BA Intermittent operation at T0 ≥ A°C
(heating mode)
0000: continuous operation
0001: 20°C, ···, 0006: -5°C
0000: continuous
operation
BB Intermittent operation at T0 < B°C
(cooling mode)
0000: continuous operation
0001: 35°C, ···, 0003: 25°C
0000: continuous
operation
BC Pump off time during thermostat off operation 0000: 5 min, ···, 0005: 30 min 0001: 10 min
680 0 - 10 V input setting 0000: Not use
0001: Temperature setting
0002: Capacity setting of Heating / Cooling
0003: Capacity setting of Hot water supply
0004: Capacity setting of Heating / Cooling +
Hot water supply
0000: Not use
681 0 - 10 V Hot water supply temperature setting 0000: Not use AI
0002: AI 2
0001: AI 1
0003: AI 3
0000: Not use AI
682 0 - 10 V Heating ZONE1 temperature setting 0000: Not use AI
0002: AI 2
0001: AI 1
0003: AI 3
0000: Not use AI
683 0 - 10 V Heating ZONE2 temperature setting 0000: Not use AI
0002: AI 2
0001: AI 1
0003: AI 3
0000: Not use AI
684 0 - 10 V Cooling temperature setting 0000: Not use AI
0002: AI 2
0001: AI 1
0003: AI 3
0000: Not use AI
685 0 - 10 V Hot water supply temperature upper limit 0040: 40°C - 0080: 80°C 0065: 65°C
686 0 - 10 V Heating ZONE1 temperature upper limit 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0055: 55°C
687 0 - 10 V Heating ZONE2 temperature upper limit 0020: 20°C - 0055: 55°C (401 / 601),
0065: 65°C (801 / 1101)
0055: 55°C
688 0 - 10 V Cooling temperature upper limit 0007: 7°C - 0029: 29°C 0020: 20°C
689 0 - 10 V Hot water supply temperature setting
resolution
0001: 1°C - 0005: 5°C 0005: 5°C
68A 0 - 10 V Heating ZONE1 temperature setting resolution 0001: 1°C - 0005: 5°C 0003: 3°C
68B 0 - 10 V Heating ZONE2 temperature setting resolution 0001: 1°C - 0005: 5°C 0003: 3°C
68C 0 - 10 V Cooling temperature setting resolution 0001: 1°C - 0005: 5°C 0001: 1°C
6A6 P1 pump speed control 0000: P1 pump fixed speed (depend on DN_A0
setting)
0001: P1 pump variable speed
0001: Variable speed
6A7 Pump speed control correction 0000: 100%
0002: 75%
0001 :90%
0003: 50%
0000: 100%
6AC Hot water supply mode operation cycle to prevent
water temperature drop
0000: Invalid
0001: 1H - 0050: 50H
0024: 24H
DN Item Details Factory default
* DN_11, 6B8, 6BA, 6BC are needed for PCB replacement or DN code reset procedure has been completed.