–10–
In the case of SMMS-u system including the Hot water module
M-HWM: Mid temperature Hot water module
H2, H4, H5: Height difference between indoor unit (Including HWM)
SMMS-u
Capacity code
of outdoor unit
(HP)
Maximum
indoor unit
quantity
Total capacity code of indoor units
(HP)
Standard indoor unit + M-HWM
Total capacity 65 - 115%
Standard model
MMY-MUP0801HT8P-E
8 18 5.2 to 9.2
MMY-MUP1001HT8P-E
10 22 6.5 to 11.5
MMY-MUP1201HT8P-E
12 27 7.8 to 13.8
MMY-MUP1401HT8P-E
14 31 9.1 to 16.1
MMY-MUP1601HT8P-E
16 36 10.4 to 18.4
MMY-MUP1801HT8P-E
18 40 11.7 to 20.7
MMY-MUP2001HT8P-E
20 45 13.0 to 23.0
MMY-MUP2201HT8P-E
22 49 14.3 to 25.3
MMY-MUP2401HT8P-E
24 54 15.6 to 27.6
MMY-UP2611HT8P-E 26 58 16.9 to 29.9
MMY-UP2811HT8P-E 28 63 18.2 to 32.2
MMY-UP3011HT8P-E 30 64 19.5 to 34.5
MMY-UP3211HT8P-E 32 65 20.8 to 36.8
MMY-UP3411HT8P-E 34 66 22.1 to 39.1
MMY-UP3611HT8P-E 36 67 23.4 to 41.4
MMY-UP3811HT8P-E 38 68 24.7 to 43.7
MMY-UP4011HT8P-E 40 69 26.0 to 46.0
MMY-UP4211HT8P-E 42 70 27.3 to 48.3
MMY-UP4411HT8P-E 44 71 28.6 to 50.6
MMY-UP4611HT8P-E 46 72 29.9 to 52.9
MMY-UP4811HT8P-E 48 73 31.2 to 55.2
MMY-UP5011HT8P-E 50 74 32.5 to 57.5
MMY-UP5211HT8P-E 52 75 33.8 to 59.8
MMY-UP5411HT8P-E 54 76 35.1 to 62.1
MMY-UP5611HT8P-E 56 77 36.4 to 64.4
MMY-UP5811HT8P-E 58 78 37.7 to 66.7
MMY-UP6011HT8P-E 60 79 39.0 to 69.0
MMY-UP6211HT8P-E 62 80 40.3 to 71.3
MMY-UP6411HT8P-E 64 81 41.6 to 73.6
MMY-UP6611HT8P-E 66 82 42.9 to 75.9
MMY-UP6811HT8P-E 68 83 44.2 to 78.2
MMY-UP7011HT8P-E 70 84 45.5 to 80.5
MMY-UP7211HT8P-E 72 85 46.8 to 82.8
MMY-UP7411HT8P-E 74 86 48.1 to 85.1
MMY-UP7611HT8P-E 76 87 49.4 to 87.4
H2, H4, H5: Height difference between indoor unit (Including HWM)
▼ Capacity code of Mid temperature Hot water module
The capacity code of the Hot water module is different from the capacity code of the standard indoor unit.
▼ Capacity code of standard indoor unit
SMMS-u
Capacity code
of outdoor unit
(HP)
Maximum
indoor unit
quantity
Total capacity code of indoor units
(HP)
Standard indoor unit + M-HWM
Total capacity 65 - 115%
Standard model
MMY-UP7811HT8P-E 78 88 50.7 to 89.7
MMY-UP8011HT8P-E 80 90 52.0 to 92.0
MMY-UP8211HT8P-E 82 92 53.3 to 94.3
MMY-UP8411HT8P-E 84 94 54.6 to 96.6
MMY-UP8611HT8P-E 86 96 55.9 to 98.9
MMY-UP8811HT8P-E 88 98 57.2 to 101.2
MMY-UP9011HT8P-E 90 100 58.5 to 103.5
MMY-UP9211HT8P-E 92 102 59.8 to 105.8
MMY-UP9411HT8P-E 94 104 61.1 to 108.1
MMY-UP9611HT8P-E 96 106 62.4 to 110.4
MMY-UP9811HT8P-E 98 108 63.7 to 112.7
MMY-UP10011HT8P-E
100 110 65.0 to 115.0
MMY-UP10211HT8P-E
102 112 66.3 to 117.3
MMY-UP10411HT8P-E
104 114 67.6 to 119.6
MMY-UP10611HT8P-E
106 116 68.9 to 121.9
MMY-UP10811HT8P-E
108 118 70.2 to 124.2
MMY-UP11011HT8P-E
110 120 71.5 to 126.5
MMY-UP11211HT8P-E
112 122 72.8 to 128.8
MMY-UP11411HT8P-E
114 124 74.1 to 131.1
MMY-UP11611HT8P-E
116 126 75.4 to 133.4
MMY-UP11811HT8P-E
118 128 76.7 to 135.7
MMY-UP12011HT8P-E
120 128 78.0 to 138.0
Mid temperature Hot water module MMW-UP0271LQ-E MMW-UP0561LQ-E
Capacity rank type 027 056
Capacity code Equivalent to HP (HP) 2.5 5
Equivalent to capacity (kW) 7.1 14.0
Capacity rank type 005 007 009 012 015 018 024 027
Capacity code Equivalent to HP (HP) 0.6 0.8 1 1.25 1.7 2 2.5 3
Equivalent to capacity (kW) 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0
Capacity rank type 030 036 048 056 072 096
Capacity code Equivalent to HP (HP) 3.2 4 5 6 8 10
Equivalent to capacity (kW) 9.0 11.2 14.0 16.0 22.4 28.0
19-EN 20-EN