–36–
F07 F07
01: TL1 sensor
02: TL2 sensor
03: TL3 sensor
TL1,TL2 or TL3 sensor trouble I/F
F08 F08 — TO sensor trouble I/F
F09 F09
01: TG1 sensor
02: TG2 sensor
03: TG3 sensor
TG1,TG2 or TG3 sensor trouble I/F
F10 — — Indoor unit TA sensor trouble Indoor unit
F12 F12
01: TS1 sensor
03: TS3 sensor
TS1 or TS3 sensor trouble I/F
F13 F13
01: Comp. 1 side 1d: Comp. 1 side
02: Comp. 2 side 2d: Comp. 2 side
03: Comp. 3 side
TH sensor trouble Compressor inverter
F15 F15 — Outdoor unit temp. sensor miswiring (ТЕ, TL) I/F
F16 F16 — Outdoor unit pressure sensor miswiring (Pd, Ps) I/F
F19 — — Hot water module TCJ2 (TF) sensor trouble Hot water module
F22 F22 — TD3 sensor trouble I/F
F23 F23 — Ps sensor trouble I/F
F24 F24 — Pd sensor trouble I/F
F25 — — Hot water module TWI (TA) sensor trouble Hot water module
F26 — — Hot water module TWO (TC2) sensor trouble Hot water module
F29 — — Indoor unit other trouble Indoor unit
F31 F31 — Indoor unit EEPROM trouble I/F
H01 H01
01: Comp. 1 side 1 : Comp. 1 side
02: Comp. 2 side 2 : Comp. 2 side
03: Comp. 3 side
Compressor break down Compressor inverter
H02 H02
01: Comp. 1 side 1 : Comp. 1 side
02: Comp. 2 side 2 : Comp. 2 side
03: Comp. 3 side
Compressor trouble (lock) Compressor inverter
H03 H03
01: Comp. 1 side 1 : Comp. 1 side
02: Comp. 2 side 2 : Comp. 2 side
03: Comp. 3 side
Current detect circuit system trouble Compressor inverter
H04 H04 — Comp. 1 case thermostat operation I/F
H05 H05 — TD1 sensor miswiring I/F
H06 H06 — Low pressure protective operation I/F
H07 H07 — Oil level down detective protection I/F
H08 H08
01: TK1 sensor trouble
02: TK2 sensor trouble
03: TK3 sensor trouble
04: TK4 sensor trouble
05: TK5 sensor trouble
Oil level detective temp. sensor trouble I/F
H14 H14 — Comp. 2 case thermostat operation I/F
H15 H15 — TD2 sensor miswiring I/F
H16 H16
01: TK1 oil circuit system trouble
02: TK2 oil circuit system trouble
03: TK3 oil circuit system trouble
04: TK4 oil circuit system trouble
05: TK5 oil circuit system trouble
Oil level detective circuit trouble I/F
H17 H17
1 : Comp. 1 side
2 : Comp. 2 side
Compressor trouble (step-out) Compressor inverter
H25 H25 — TD3 sensor miswiring I/F
Check code
Check code name Judging device
Wired remote
controller display
Outdoor unit 7-segment display
Auxiliary code
71-EN 72-EN