127
Check code
Location
of
detection
Description System status Error detection condition(s) Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
P07 P07
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU
I/F
Heat sink
overheating
error
All stop Temperature sensor built into
IGBT (TH) is overheated.
Check power supply voltage.
Check outdoor fan system error.
Check heat sink cooling duct for
clogging.
Check IGBT and heat sink for
thermal performance for faulty
installation.
(e.g. mounting screws and
thermal conductivity)
Check for defect in A3-IPDU.
(faulty IGBT built-in temperature
sensor (TH))
P10 P10
Detected indoor
address
Indoor
unit
Indoor overflow
error
All stop Float switch operates.
Float switch circuit is open-
circuited or disconnected at
connector.
Check float switch connector.
Check operation of drain pump.
Check drain pump circuit.
Check drain pipe for clogging.
Check for defect in indoor P.C.
board.
P12
Indoor
unit
Indoor fan motor
error
Stop of
corresponding
unit
Motor speed measurements
continuously deviate from target
value.
Overcurrent protection is
activated.
Check connection of fan
connector and wiring.
Check for defect in fan motor.
Check for defect in indoor P.C.
board.
Check impact of outside air
treatment (OA).
P13 P13
I/F Outdoor liquid
backflow
detection error
All stop <During cooling operation>
When system is in cooling
operation, high pressure is
detected in follower unit that has
been turned off.
<During heating operation>
When system is in heating
operation, outdoor PMV 1 or 2
continuously registers opening of
100p or less while under SH
control.
Check full-close operation of
outdoor PMV (1, 2, 4).
Check for defect in Pd or Ps
sensor.
Check gas balancing circuit
(SV2) for clogging.
Check balance pipe.
Check SV3B circuit for clogging.
Check defect in outdoor P.C.
board (I/F).
Check capillary of oil separator oil
return circuit for clogging.
Check for leakage of check valve
in discharge pipe convergent
section.
P15 P15
01: TS condition I/F Gas
leakdetection
(TS1 condition)
All stop Protective shutdown due to
sustained suction temperature at
or above judgment criterion
for at least 10 minutes is repeated
four times or more.
<TS error judgment criterion>
In cooling operation: 140 °F (60
°C)
In heating operation: 104 °F (40
°C)
Check for insufficiency in
refrigerant quantity.
Check outdoor service valves
(gas side, liquid side) to confirm
full opening.
Check PMVs (PMV1, 2) for
clogging.
Check resistance characteristics
of TS1 sensor.
Check for defect in 4-way valve.
Check SV4 circuit for leakage
02: TD condition I/F Gas leak
detection
(TD condition)
All stop Protective shutdown due to
sustained discharge temperature
(TD1, TD2 or TD3) at or above
226.4 °F (108 °C) for at least 10
minutes is repeated four times or
more.
Check for insufficiency in
refrigerant quantity.
Check PMVs (PMV 1, 2) for
clogging.
Check resistance characteristics
of TD1, TD2 and TD3 sensors.
Check indoor filter for clogging.
Check piping for clogging.
Check SV4 circuit (for leakage or
coil installation error).
P17 P17
I/F Discharge
temperature
TD2 error
All stop Discharge temperature (TD2)
exceeds 239 °F (115 °C).
Check outdoor service valves
(gas side, liquid side) to confirm
full opening.
Check outdoor PMVs (PMV1, 2,
4) for clogging.
Check resistance characteristics
of TD2 sensor.
Check for defect in 4-way valve.
Check SV4 circuit for leakage.
Check SV4 circuit (for wiring or
installation error involving SV41,
SV42 and SV43).