Heat sink
1 Detachment
1) Take off the fixing screws. (M4 x 0.3" (8mm), 2 pcs)
2) Remove the heat sink from the coil. (SVSS or SVD)
2 Attachment
1) Fix the heat sink as before.
2) Fit the screws of the heatsink (M4 x 0.3" (8mm), 2 pcs)
at a torque of 1.08 ftlbs (1.47 ± 0.1 Nm).
2 Attachment
1) Fix the coil and the Coil connection plate as before and fit the screws.
2) Connect the wires disconnected as before.
3) Fix wires of coils (SVS, SVSS, SVDD, SVD) by the wire clamp.
4) Attach the Electric parts cover and the Top plate. (Refer to 1. -2) and 5. -2))
Fix the heatsink to the direction indicated in the figure.
Attach the coil to the position indicated in the coil attachment nameplate.
Be careful about the attachment directions of the coil .
Fixing screw size
SVS ,SVSS ,SVDD,SVD : M4x0.24" (6mm)(each 1 pc)
Control tightening torque of the coil with 1.47 ± 0.7 ftlbs (2.0 ± 0.1 Nm).
Wire the lead through the lower side than the coil so that the edge
of the coil do not damage the lead.
Screws
Upper side
SVSS or SVD
269