– 101 –
6-5. Method to Set Indoor Unit Function DN Code
When performing this task, be sure to use RBC-AMS51E
∗
or RBC-AMT32E.
For operation of RBC-AMS51E
∗
, refer to the attached manual.
<Procedure> To be performed only when system at rest
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
54
126
3
(RBC-AMT32E)
1 Push the
TEST
+
SET
+
CL
buttons simultaneously and hold for at
least 4 seconds.
The unit No. displayed first is the address of the header indoor unit in
group control.
Then the fan and louver of the selected indoor unit move.
2 Each time the “Select unit” side of the
UNIT LOUVER
button is
pushed, one of the indoor unit Nos. under group control is
displayed in turn. Then the fan and louver of the selected
indoor unit move.
3 Use the
TEMP
button to select the CODE No. (DN code) of
the desired function.
4 Use the
TIME
button to select the desired SET DATA
associated with the selected function.
5 Push the
SET
button. (The display changes from flashing to
steady.)
• To change the selected indoor unit, go back to step 2.
• To change the selected function, go back to step 3.
6 When the
SET
button is pushed, the system returns to normal
off state.