– 168 –
*1 When the units are connected to a group, data of the header indoor unit only can be displayed.
*2 Only a part of indoor unit types is installed with the discharge temperature sensor. This temperature is not
displayed for other types.
*3 The first digit of an CODE No. indicates the outdoor unit number.
*4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1
, 5
... U1 outdoor unit (Header unit)
2
, 6
... U2 outdoor unit (Follower unit 1)
3
, 7
... U3 outdoor unit (Follower unit 2)
*5 Only the CODE No. 5* of U1 outdoor unit (Header unit) is displayed.
CODE No. Data name Display format Unit Remote controller display example
00
01
02
03
04
05
06
08
F3
F9
FA
0A
0B
0C
0D
Room temperature (During control) *
1
Room temperature (Remote controller)
Indoor suction temperature (TA)
Indoor coil temperature (TCJ)
Indoor coil temperature (TC2)
Indoor coil temperature (TC1)
Indoor discharge temperature (TF) *
2
Indoor PMV opening
Filter sign time
Suction temperature of air to air heat exchanger (TSA)
*
2
Outside air temperature (TOA) *
2
No. of connected indoor units
Total horsepower of connected indoor units
No. of connected outdoor units
Total horsepower of outdoor units
System data Indoor unit data *
1
×1
×1
×1
×1
×1
×1
×1
×1/10
×1
×1
×1
×1
×10
×1
×10
˚C
˚C
˚C
˚C
˚C
˚C
˚C
pls
h
˚C
˚C
unit
HP
unit
HP
[0024] = 24˚C
[0150] = 1500pls
[2500] = 2500h
[0048] = 48 units
[0415] = 41.5HP
[0004] = 4 units
[0420] = 42HP
[0024] = 24˚C
CODE No.
Data name Display format Unit Remote controller display example
U2 U3U1
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
High-pressure sensor detention pressure (Pd)
Low-pressure sensor detention pressure (Ps)
Compressor 1 discharge temperature (Td1)
Compressor 2 discharge temperature (Td2)
Compressor 3 discharge temperature (Td3)
Suction temperature (TS1)
Outdoor coil temperature 1 (TE1)
Outdoor coil temperature 2 (TE2)
Temperature at liquid side (TL)
Outside ambient temperature (TO)
PMV1 + 2 opening
PMV4 opening
Compressor 1 current (I1)
Compressor 2 current (I2)
Compressor 3 current (I3)
Outdoor fan current (IFan)
Outdoor unit individual data 1 *
3
×100
×100
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×10
×10
×10
×10
MPa
MPa
˚C
˚C
˚C
˚C
˚C
˚C
˚C
˚C
pls
pls
A
A
A
A
[0123]=1.23MPa
[0024]=24˚C
[0500]=500pls
[0135]=13.5A
CODE No.
Data name Display format Unit Remote controller display example
U2 U3U1
60
61
62
63
64
65
66
67
70
71
72
73
74
75
76
77
50
51
52
53
54
55
56
57
Compressor 1 revolutions
Compressor 2 revolutions
Compressor 3 revolutions
Outdoor fan mode
Compressor IPDU 1 heat sink temperature
Compressor IPDU 2 heat sink temperature
Compressor IPDU 3 heat sink temperature
Outdoor fan IPDU heat sink temperature
[0642]=64.2rps
[0058]= 58 mode
[0024]=24 ‹C
59
5A
Pressure release *
5
Discharge temperature release *
5
[0010]=Pressure release controlled
[0001]=
Discharge temperature release controlled
Outdoor unit individual data 2 *
4
×10
×10
×10
×1
×1
×1
×1
×1
rps
rps
rps
mode
˚C
˚C
˚C
˚C
6F 7F5F Outdoor unit horsepower [0014]=14HP×1 HP
——58 Heating/cooling recovery controlled *
5
[0010]=Heating recovery controlled
[0001]=Cooling recovery controlled
0: Normal
1: Recovery controlled
——5B
[0100]=U2 outdoor unit release controlled
[0010]=U3 outdoor unit release controlled
[0001]=U4 outdoor unit release controlled
0: Normal
1: Release controlled
Follower unit release
(U2/U2/U4 outdoor units) *
5