EasyManua.ls Logo

Toshiba MMY-MAP0804FT8(ZG)-E - Page 20

Toshiba MMY-MAP0804FT8(ZG)-E
333 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 20 –
5m
5m
OK
OK
5m
OK
NG
5m
NG
5m
Header unit
Header unit
Header unit
Follower
unit
Follower
unit
Follower
unit
Follower
unit
Follower
unit
Follower
unit
Header unit
Header unit
Follower
unit
Follower
unit
Follower
unit
Follower
unit
Selection of installation place
EThe cooling performance may decline considerably when total operating capacity of cooling indoor units is
less than 4 HP while ambient temperature is below 0°C.
EWhen system capacity is greater than 28 HP, height difference between indoor units is limited to 3 m. If the
piping exceeds 3 m with a capacity greater than 28 HP there may be a case of capacity shortage in cooling.
Height between outdoor units
Ensure that the header unit is installed below all connected follower outdoor unit(s).
Possible product failure may occur if header unit is installed above any follower unit(s).
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Table of Contents

Related product manuals