Selection of installation place
• EThe cooling performance may decline considerably when total operating capacity of cooling indoor units is
less than 4 HP while ambient temperature is below 0°C.
• EWhen system capacity is greater than 28 HP, height difference between indoor units is limited to 3 m. If the
piping exceeds 3 m with a capacity greater than 28 HP there may be a case of capacity shortage in cooling.
Height between outdoor units
Ensure that the header unit is installed below all connected follower outdoor unit(s).
Possible product failure may occur if header unit is installed above any follower unit(s).