NO. Item Specification outline Remarks
4 Automatic
capacity
control
1. The outdoor unit determines the operational capacities of indoor units according to
the difference between Ta and Ts.
Ts: Temperature
setting
Ta: Room
temperature
SD
SB
S9
S7
S5
S3
S0
Cooling
+2
+1
Ts
-1
S3
S5
S7
S9
SB
SD
SF
S0
Heating
+1
Ts
-2
-1
Ta
(˚C)
Ta
(˚C)
5 Fan speed
control
1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED (H)”, “LOW
(L)” and “AUTO” on the basis of a command issued via the remote controller.
(Concealed duct high static pressure type: HH only)
2. In AUTO fan speed mode, the air speed changes according to the difference
between Ta and Ts.
<Cooling>
HH > H+ > H >
L+ > L > UL
or LL
-0.5
Tsc
+0.5
+1.0
+1.5
+2.0
+2.5
+3.0
Ta (˚C)
HH
H
L
L
L
H+
L+
A
B
C
D
E
F
G
<HH>
<HH>
<HH>
<HH>
<H>
<H>
<L+>
• Control is identical in remote controller thermo and body thermo operation.
Speed modes shown in < > apply to cooling operation under AUTO air
conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each
time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of cooling operation, a higher speed (steeper downward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed
stays the same.
<Heating>
+4.0
+3.0
+2.0
+1.0
Tsh
-1.0
Ta (˚C)
(+2.0)
(+1.5)
(+1.0)
(+0.5)
(0)
(-0.5)
L
L+
H
H+
HH
E
D
C
B
A
<L+>
<H>
<H+>
<HH>
<HH>
Figures inside ( ) applies to remote controller thermo operation.
Figures outside ( ) applies to body thermo operation.
Speed modes shown in < > apply to heating operation under AUTO air conditioner
operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 1 minute each
time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of heating operation, a higher speed (steeper upward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed
stays the same.
• When TC2 ≥ 60 °C, the fan speed is raised by one step.
DN code “32”
“0000”: Body thermo
“0001”: Remote
controller thermo
TC2: Indoor heat
exchanger sensor
temperature