101
5d
High-ceiling adjustment
(Air flow selection)
1-way air discharge cassette (SH)
2-way air discharge cassette
* The high-ceiling installation of model AP007 to AP012 can only be
undertaken when the combined capacity of the indoor units connected is
100% or less than the capacity of the outdoor unit.
Do not proceed with high-ceiling installation if this limit is exceeded.
4-way air discharge cassette
Under ceiling
0000: Standard
Built-in filter 2-way air discharge cassette
0000: Standard filter (factory default)
0001: Super long-life filter
4-way air discharge cassette
0000: Standard filter (factory default)
Under ceiling
0000: Standard filter (factory default)
Concealed duct standard
0000: Standard filter (factory default)
0001: High-performance filter (65%, 90%)
Static pressure selection Concealed duct standard
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: Low static pressure
Slim Duct
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: High static pressure 3
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable (cannot be
performed)
0000: Available
DN Item Description At shipment
Value Type AP015, AP018 AP024
0000 Standard (factory default) 3.5 m or less 3.8 m or less
0001 High-ceiling (1) 4.0 m or less 4.0 m or less
0003 High-ceiling (3) 4.2 m or less 4.2 m or less
Value Type AP007~AP030 AP036~AP056
0000 Standard (factory default) 2.7 m or less 2.7 m or less
0001 High-ceiling (1) 3.2 m or less (*) 3.0 m or less
0003 High-ceiling (3) 3.8 m or less (*) 3.5 m or less
Value
Type AP009~AP012 AP015~AP018
Air flow at outlet
4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
0000
Standard
(factory default)
2.7 m 2.8 m 3.0 m 2.8 m 3.2 m 3.5 m
0001 High-ceiling (1) 3.2 m 3.5 m 3.8 m
0003 High-ceiling (3) 3.5 m 3.8 m
Value
Type AP024~AP030 AP036~AP056
Air flow at outlet
4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
0000
Standard
(factory default)
3.0 m 3.3 m 3.6 m 3.0 m 3.3 m 3.6 m
0001 High-ceiling (1) 3.3 m 3.5 m 3.8 m 3.3 m 3.5 m 3.8 m
0003 High-ceiling (3) 3.6 m 3.8 m 3.6 m 3.8 m
Value Type AP015~AP056
0000 Standard (factory default) 3.5 m or less
0001 High-ceiling (1) 4.0 m or less