EasyManua.ls Logo

Toshiba MMY-MAP0806HT8P-E - Page 73

Toshiba MMY-MAP0806HT8P-E
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
144-EN143-EN
– 72 –
Be sure to keep the rule of below tables about size and length of communication wiring.
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A
B
U3 U4
U1
U2
U5 U6
U1
U2
A
B
U1 U2
A B
U1 U2
A B
U1 U2
A
B
U3
U4
U1
U2
U5 U6
U3
U4
U1 U2
U5 U6
U3
U4
U1 U2
U5
U6
U1 U2
A B
U1 U2
A
B
U1 U2
A B
U3 U4
U1 U2
U5
U6
L1
L5
L6
L7
L4
3L2L
Central
control
controller
Header
unit
Header
unit
Header
unit
Follower
unit
Follower
unit
Follower
unit
Indoor unit
Outdoor unit
Remote controller Remote controller
Remote controller
Table-3
Super modular multi system
Table-1
Table-1
Table-2
Table-1
Table-2
Table-3
Table-3
Table-1
Table-1 Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm
2
: Up to 1000 m/2.0 mm
2
: Up to 2000 m (*1)
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
Table-2 Communication wiring between outdoor units (L5)
Wiring 2-core, non-polarity
Type Shield wire
Size/Length 1.25 mm
2
to 2.0 mm
2
/Up to 100 m (L5)
Table-3 Remote controller wiring (L6, L7)
Wiring 2-core, non-polarity
Size 0.5 mm
2
to 2.0 mm
2
Length
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
¿ Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
AB AB AB AB AB AB
(A.B)
Indoor unit
No.1 No.2 No.3 No.4 No.7 No.8
Remote controller
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power
and communication wires through the holes.
Knockout for the
communication wire
Knockout for the power
wire
Knockout for the power
supply wire
Piping/wiring panel
NOTE
Be sure to separate the power wire and communication wires.
1117101201-3 EN.indd 721117101201-3 EN.indd 72 8/8/2559 BE 3:49 PM8/8/2559 BE 3:49 PM