JK0-B2F
Power supply terminal block
Clamp lter
(only MAP180 to MAP220 type)
Cord clamps
Communication terminal block
Power supply wires
Cord clamp
Communication wires
Earth screw
¿ Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power
supply wire to the power supply terminal block and the earth line to the earth screw. After that, x the power
supply wire with the 2 cord clamps.
2. Be sure to use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to x the terminal screws.
L1
L2 L3 N
L1 L
2
L
3
N
10mm or more
Attached clamp lter
Fixed on attached binding band
(only MAP180 to MAP220 type)
Earth line
Power supply wire
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Power supply terminal M6 2.5 to 3.0
Earth screw M8 5.5 to 6.6
¿ Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the
communication wire terminals, then x it with the communication cable clamp.
U1
U3
U4
U2
U5
U6
S
S
TO
INDOOR
UNIT
TO
OUTDOOR
UNIT
TO
CENTRAL
CONTROLLER
SHIELD SHIELD
U5, U6: Communication wiring between outdoor units
U
3, U4: Central control device
U1, U2: Communication wiring between indoor/outdoor units
S: Shield wire earth
Screw size and tightening torque
Screw size
Tightening torque
(N•m)
Communication wire terminal M4 1.2 to 1.4