129
A
A.5 Use of BUM7B by Application
Examples of BUM7B configuration are shown in this section.
BUM7B can be used as the main or remote base unit.
The tables below show the usage and operation of BUM7B.
Table A.6 Main / remote base unit
Model Usage
No. of space
slots
No, of mountable
I/O modules
Remarks
BUM7B Main base unit 1 10
PUM12 is
mounted in S0.
Remote base unit 0 11
GA922 is
mounted in S0.
Table A.7 Mountable modules on the main base unit (○: mountable, ×: not mountable)
Model BUM7B
Module type
Slot No.
S0 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11
PUM12 ○ × × × × × × × × × × ×
G2 I/O with interrupt
function
× ○ ○ ○ ○ ○ ○ ○ ○ × × ×
G2 I/O without interrupt
function
× ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ×
Table A.8 Mountable modules on the remote base unit (○: mountable, ×: not mountable)
Model BUM7B
Module type
Slot No.
S0 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11
GA922 ○ × × × × × × × × × × ×
G2 I/O with interrupt
function
× × × × × × × × × × × ×
G2 I/O without interrupt
function
× ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Table A.9 I/O module addresses according to the usage
Model BUM7B
Usage
Slot No.
S0 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11
Main base unit × ⓪ ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ -
Remote base unit × ⓪ ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩
S: Slot number
Circled number: Module address