T series Migration User’s Manual - Hardware -
49
2
2.3 T3 Series
There are two ways of migration to T3 series PUM11/PUM12:
Changing the G3 I/O module to the G2 I/O module
Retaining the G3 I/O module
For retaining the G3 I/O module, refer to 2.4.
2.3.1 CPU Module
The T3 series CPU modules (T3/T3H/T3V
*
) are converted to PUM11/PUM12 using the
T-PDS conversion tool.
Table 2.22 T3 series CPU module conversion
After conversion
Before conversion
nv controller type1 light
PUM11 PUM12 PUM14
PROSEC
T series
T3
PU315 ○ ○ ×
PU325 ○ ○ ×
T3H
PU325H ○ ○ ×
PU326H ○ ○ ×
T3V
*
PU325V ○ ○ ×
PU326V ○ ○ ×
○: Selectable, ×: Not selectable
*: For the conversion of T3V, refer to the same conversion
procedure for T3H.
Table 2.23 Comparison of CPU module/controller module specifications
T3 T3H nv controller type1 light
Model PU315/325 PU325H PU326H PUM11 PUM12
Applicable I/O G3 I/O G3 I/O G2 I/O
Development tool TPDS TPDS Engineering tool
Station bus No No No Yes
Program capacity 32k step 32k step 64k step 32k step 64k step
Programing language LD,SFC LD,SFC LD,SFC,FBD,ST
I/O registers 256W 512W 3kW
Data registers 8kW 8kW 8kW
Execution
speed
Contact 0.15us 0.1us 0.08us 0.04us
Coils 0.3us 0.2us 0.16us 0.08us
Moving 0.98us 0.54us 0.08us 0.04us
Add 2.25us 0.9us 0.08us 0.04us
Transmission
port
Tool
connection
RS232C RS232C USB
Computer
Link
RS485 RS485 RS485
Ethernet
No No
Yes
Others - - - TC-net I/O
◆Remark:
Not all specifications are listed in the above comparison table.
Confirm the specification in the relevant instruction manual.