Chapter 3 Installation and Wiring
6F8C1497
74
Table 3-1 Installation environment
Item Specifications Remarks
Operating ambient
temperature
0 to 55°C, 24-hour average temperature 40°C or
less
(Note 1)
Storage
temperature
-
40-70°C
Operating ambient
relative humidity
10 to 95%RH, level RH2 (no condensation) (Note 2)
Dust Dust 0.3mg/m
3
(no conductive dust)
Degree of
contamination
2 (usually, no conductive contamination) or less IEC 61131-2
Corrosive gas No corrosive gasses
No silicon-containing substances
(Note 3)
Usable altitude Up to 2000m above sea level
Vibration
resistance
(vibration
immunity)
IEC 60068-2-6, test Fc-compliant X, Y, Z
10 cycles each
(Note 4)
Shock resistance
(shock immunity)
IEC 60068-2-27, test Ea-compliant 147m/S
2
(Three times each in three orthogonal axis
directions)
Noise resistance
First
transient
AC power supply: 2kV
DC power supply: 2kV (10m or less unnecessary)
I/O power supply DC: 1kV (10m or less
unnecessary)
AC-I/O: 2kV (unshielded cable)
DC-I/O: 1kV (unshielded cable)
Analog I/O: 1kV (shielded cable)
Electrostatic
discharge
4kV (contact discharge), level ESD-3
Radiation field
level
10V/m
Impulse noise Power supply line Noise voltage: 1500V,
Pulse width: 1µs/100ns
EMC zone Zone B (including Zone A)
Grounding Class D grounding (Note 5)
Structure Open-type equipment
Installation
location
Inside of indoor control panel
Cooling method Naturally-cooled
(Note 1) The reference temperature measurement position is 50mm below the bottom of the base
unit.
(Note 2) For long-term storage, store spare parts in dark places and avoid hot or wet places.
For the product in long-term storage, the temperature and humidity shall be 0 to 40°C and
20 to 80%RH (no condensation) and the temperature change rate shall be 10°C/h or less.
Particularly store batteries and power supplies at the room temperature (25°C) or less as
their estimated usable periods are affected by high ambient temperatures.