Unified Controller nv Series type1 light Controller Unit Operating Instructions
77
3.3 Mounting to Chassis
Figure 3-1 shows the example of mounting the controller unit. In this figure, the controller
unit, incoming power distribution unit, terminal block unit, and others are mounted.
Figure 3-1 Example of mounting controller unit in chassis
Keep the temperature inside the chassis 55°C or less around the T series migration system.
The product life is specified at the equipment ambient temperature of 40°C. If the
temperature exceeds 40°C, set the maintenance and replacement time by considering life
shortening.