Chapter1 Overview
6F8C1370
4
1.2. PI918 function setting parameters
Thefollowingfunctionsettingparameterscanbespecifiedfromthe
controllerwhenthePI918startsup.
TheparameterscanbesetwhenthePI918isregisteredinthecontroller
side.
1.2.1. Module parameter (common function setting)
Thefollowingsettingsarecommonamongalltheinputchannels.
Common parameter
Setting
value
Function
Gatebatchpermission
(GEN)
0
Doesnotsetgatebatchpermission. ON/OFF
controlisdonebyusinggateinputofeach
channel.
1
Setsgatebatchpermission. Gateinputofall
channelsisregardedasON(‘1’).
Inputfiltersetting
(LSF)
0 Inputfilterforhighspeed(50kHz-max.)
1
Inputfilterforlowspeed(50Hz-max.,contact
supported)
Speedcounter
frequencysetting
(TM-2bit)
00 Setsspeedcountercycleof1s.
01 Setsspeedcountercycleof0.5s.
10 Setsspeedcountercycleof0.2s.
11 Setsspeedcountercycleof0.1s.
Internalreference
pulsesetting(FQ-2bit)
00 Internalreferencepulse100Hz
01 Internalreferencepulse1kHz
10 Internalreferencepulse10kHz
11 Internalreferencepulse50kHz
Table 1.2.1. Common parameters
1.2.2. Point parameter (function setting by channel)
Thefollowingcanbesetforeachinputchannel.
Point parameter
Setting
value
Function
Externalpulse
specification(EP)
0 Countstheinternalcommonreferencepulses.
1 Countstheindividualexternalinputpulses.
Alarmsetting(AL)
0 Doesnotsetalarm
1 Setsalarm
Speedmodesetting
(SP)
0 Normalcounter
1 Setsspeedcounter.
Slavemodesetting
(SV)
0 Normal(master;operatesindependently)
1
Slave(synchronizeswithstart/stopofthe
previouschannel)