Chapter 2 Installing/Uninstalling
6F8C1575
26
2.2 Implementation to the Chassis
An example of installing the controller unit is shown in Figure 2-2. The figure illustrates
the installation of the controller unit, power distribution unit and terminal block unit
Figure
2-2
Example of implementing the controller unit on the chassis
The temperature in the chassis should be 0°C- 55°C around the controller unit. The life
of the product is specified based on the reference temperature of 40°C. If the operating
temperature exceeds 40°C, determine the time for maintenance and replacement by
taking a shorter service life into account.
Note
・
Decide the location to install the TC-net I/O base taking the length of the cable into
consideration.
Fan unit
Controller unit
Power
distribution unit
Ethernetrelay
connector
Fan unit
Terminal block unit
TC-netI/Omodule
Communication
baseunit
Communication module
I/O system power unit
External power unit
Ethernetrelay
panel