112 P9 ASD Installation and Operation Manual
RR Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RR input level that is associated with RR Input Point 2
Frequency when operating in the Speed control mode or is associated with the
RR Input Point 1 Rate when operating in the Torque Control mode.
This value is entered as 0% to 100% of the RR input signal range.
See RR Input Point 1 Setting (F210) for additional information on this
parameter when used for Speed control.
See RR Input Point 1 Rate (F214) for additional information on this parameter
when used for Torque Control.
Direct Access Number — F212
Parameter Type — Numerical
Factory Default 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
RR Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RR Input Point 2 Frequency and is the frequency that is
associated with the setting of RR Input Point 2 Setting when operating in the
Speed Control mode.
See RR Input Point 1 Setting (F210) for additional information on this
parameter.
Direct Access Number — F213
Parameter Type — Numerical
Factory Default 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
F212 F213