122 P9 ASD Installation and Operation Manual
BIN Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the BIN input terminals when the
BIN terminals are used as the control input.
This parameter sets BIN Input Point 1 Frequency and is the frequency that is
associated with the setting of BIN Input Point 1 Setting.
See BIN Input Point 1 Setting (F228) for additional information on this
setting.
Direct Access Number — F229
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0
Maximum — Maximum Freq. (F011)
Units — Hz
BIN Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the BIN input terminals when the
BIN terminals are used as the control input.
This parameter sets the BIN input signal that is associated with BIN Input
Point 2 Frequency.
This value is entered as 0% to +100% of the BIN input signal range.
See BIN Input Point 1 Setting (F228) for additional information on this
setting.
Direct Access Number — F230
Parameter Type — Numerical
Factory Default 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
BIN Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the BIN input terminals when the
BIN terminals are used as the control input.
This parameter sets BIN Input Point 2 Frequency and is the frequency that is
associated with the setting of BIN Input Point 2 Setting.
See BIN Input Point 1 Setting (F228) for additional information on this
setting.
Direct Access Number — F231
Parameter Type — Numerical
Factory Default 60.00
Changeable During Run — Yes
Maximum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
F229 F231