132 P9 ASD Installation and Operation Manual
Jump Frequency 1 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 1
(
F270).
Direct Access Number — F271
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program Special Jump Frequencies
This parameter is the same as Jump Frequency 1 (F270) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
F273). When multiple jump frequencies overlap, the system will recognize the
lowest and the highest frequencies as one jump range.
Direct Access Number — F272
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Jump Frequency 2 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 2
(
F272).
Direct Access Number — F273
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program Special Jump Frequencies
This parameter is the same as Jump Frequency 1 (F270) and is used when
multiple frequencies are to be jumped (see the plus-or-minus value setting at
F275).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Jump Frequency 3 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(
F274).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Preset Speed 8
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed.
See F018 for additional information on this parameter.
Direct Access Number — F287
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — Lower-Limit Freq. (F013)
Maximum — Upper-Limit Freq. (F012)
Units — Hz
F271 F287