144 P9 ASD Installation and Operation Manual
Acceleration Suspend Time
Program Fundamental Accel/Decel 1 Settings
When Enabled at F349, this parameter is used to set the duration of activation
of the Acceleration Suspend function when initiated by reaching the
Acceleration Suspend Frequency setting (
F350).
Once this parameter times out, the acceleration rate will resume from the point
of suspension.
Direct Access Number — F351
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
Deceleration Suspend Frequency
Program Fundamental Accel/Decel 1 Settings
When Enabled at F349, this parameter is used to set the frequency at which the
Deceleration Suspend function will activate.
During deceleration, this parameter sets the frequency at which deceleration
will stop and the motor will run at the setting of this parameter for the time
setting of F353.
Direct Access Number — F352
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Deceleration Suspend Time
Program Fundamental Accel/Decel 1 Settings
When Enabled at F349, this parameter is used to set the duration of activation
of the Deceleration Suspend function when initiated by reaching the
Deceleration Suspend Frequency setting (
F352).
Once this parameter times out, the deceleration rate will resume from the point
of suspension.
Direct Access Number — F353
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
F351 F353