V/I Analog Input Loss Response
Program Ter mi nal Input Special Functions
This parameter is used to provide a system disposition in the event of the loss of
the V/I input signal.
The system will either trip, run the speed set at Preset Speed 14, or run at the
F456 setting in the Direct mode.
Note: Preset Speed 14 must be configured to use the preset speed
selection.
Settings:
0 — Trip
1 — Preset Speed 14
2 — Direct Mode Speed Setpoint (Run at F456 setting)
Direct Access Number — F644
Parameter Type — Selection List
Factory Default Trip
Changeable During Run — No
Adding Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
5 — EOI (Keypad)
6 — RS485 (2-Wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (Terminal Board)
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F660
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the commanded frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the commanded frequency.
If Setting (F729) is selected, the % value entered at parameter F729 is used as
the multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Setting (F729)
5 — RX2 Option (AI1)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — Yes
F644 F661